Detailed product view
Part number: 850934

CIRCULATING COOLANT AND AIR WASHER Neomeris Control DOS

Field of application:
Micro-Controller Neomeris Control DOS for time-depending biocide dosing at cooling water loops and air washers.

Product description (CIRCULATING COOLANT AND AIR WASHER Neomeris Control DOS):

Performance profile:

  • Graphic display 128x64 pixel, RGB backlight, membrane keypad
  • Operating language: D and GB
  • Time-dependent dosing of conditioning agent via dosing pump
  • Start/Stop-mode dosing pump
  • Blowdown interlocking during residence time of the biocide
  • Interconnection of blowdown locking with system pump
  • Time programming for dosing 1–4
  • PC software for parameter setup and visualization (optional)

Connections:

  • Output for circulation pump: changeover contact, 250 V, max. 4 total
  • 3 relay outputs for dosing pump, biocide lockout blowdown, alarm
  • Switching input: biocide empty message

Technical Data:

  • Protection class: IP65
  • Main connections: 100-200 VAC, 50-60 Hz
  • Power consumption: 5 A AC
  • Dimensions (W x H x L): approx. 199 x 179 x 106 mm


 
 
 