Detailed product view
Part number: 100630

Testomat® 808 SiO2

Measuring parameter:
Silicat SiO2
Measuring range:
Silicat SiO2: 0.3 - 1.2 ppm
Field of application:
sterilisation of hospitals | silicat monitoring |
Maximum media temp. [°C]:
10 to 40 °C; 50 to 104°F

Product description (Testomat® 808 SiO2):

The Testomat® 808 SiO2 has been designed for use in the sterilisation of hospitals. It complies with the EN 285:2006 standard. The device is a limit gauge that automatically monitors the level of SiO2 in the water. You have a choice between 10 limits in the range of 0.3 to 1.2 ppm.

Technical Data

Power supply: Dependig on product configuration: 24V / 115V / 230V, 50 – 60 Hz
Instrument protection: 230 – 240 V: T0,1 A; 115 V: T0,2 A; 24 V: T0,8 A
Mains protection for consumers: max. 4 A (N , L)
Power consumption: max. 16 VA, without external load
Protection class: I
Degree of protection: IP 54
Conformity: EN 61000-6-2, EN 61000-6-4, EN 61010-1
Ambient temperature: 10 – 40 °C; 50 - 104°F
Current interface: Output of defined values (5, 8, 11, 14, 17, 20 mA) for displaying status and error mes-sages, max. load 500 Ohms
Contact load relay: 230V / 4A AC ohm resistive load
Dimensions: B x H x T = 364 x 314 x 138 mm; with side pocket: 442 x 314 x 138 mm
Weight: 4350 g

 



 
 
 
To the top